.
Our site needs your help!
Site categories
1/ Help
:

Questions and answers to Crew Evaluation System Test about Diesel Generator

Join Our Telegram (Seaman Community)

This page contains answers to Seagull CES test about Diesel Generator on ship, and serve as a database of questions and answers, using which seafarer can prepare to exams for getting certificate of competence, or just to challenge yourself with knowledge in this theme.



CBT CD 0041 – Generator.pdf

Download

Use the search below to find question.

Amount of questions: 26.

Right answers marked with this sign .

During the parallel operation of generators, the operator adjusts the diesel generator no. 1’s potmeter in the main switchboard to a higher resistance. What will happen?
The main bus-bar voltage will increase.
The reactive load on diesel generator no. 1 will increase.
The reactive load on diesel generator no. 1 will increase.
How could you monitor the correct instant for synchronizing without the aid of a synchroscope or synchronizing lamps?
By connecting a pair of voltmeter probes across one phase of the incoming generator circuit breaker, and then adjust the generator speed until the voltmeter slowly fluctuates from zero to maximum. Connect the breaker when the voltmeter passes through zero.
It is not possible to synchronise generators without the synchronizing aids.
By off-loading the running generator to a minimum to avoid large “kicks” at connection. Adjust the incoming generator to a frequency slightly less than the running generator. The running generator will then “pull” the incoming generator into synchronism.
How many % of nominal voltage is required before main circuit breaker can be connected to main bus bar?
70 %.
50 %.
80 %.
90 %.
How many degrees are there between the phases in a 3-phase generator?
120°.
180°.
90°.
60°.
If we have a generator with 4 poles, how many rpm does it need to give 60 Hz?
1 800 rpm.
1 200 rpm.
900 rpm.
In a winding, which rotates in a magnetic field, the induced voltage is:
At its highest when the flux is at its lowest.
At its highest when the flux is at its highest.
At its highest when the flux change/time factor is at its lowest.
In this module we will use a diesel engine with 1 200 rpm, 60 Hz as the primary mover for the alternator. How many pole pairs are present in the alternator?
1 pole.
2 poles.
3 poles.
Normally the power factor on the generator is:
0,8-0,9.
0,9-1,0.
0,6-0,7.
The 700 kW generator circuit breaker has an over-current trip setting of 125 %. What will the actual minimum tripping current level be, when the power factor is 0,85?
1 352 A.
1 310 A.
950 A.
The diesel generator no. 1 has recently been through a major overhaul. During the running-in period, we do not want the engine to take full load. What do you do?
Change the speed drop, so that the diesel engine no. 2 will take a relatively larger part of the load.
Manually adjust the load sharing by means of the Up/Down switches on the main switchboard, until the running-in period is completed.
Change the max load setting on the governor.
The generators are run in manual, and when you discover that the DG no. 1 takes a larger part of the active load than DG no. 2, what could you do to share the load equally between the generators?
Increase the DG 1 and decrease the DG 2 by means of the governor control.
Increase the DG 2 and decrease DG 1 by means of the governor control switch.
Increase the magnetisation on DG 2 and decrease the magnetisation on DG 1.
The kW and kVAr instruments on the main switchboard reads respectively 630 kW and 400 kVAr. What is the actual power factor?
0,8.
0,85.
0,9.
The nominal frequency is 60 Hz at 1 200 rpm and speed set point (idle speed) is set to 1 200 rpm. What is the speed and frequency at 80 % load, when the speed drop is set to 4 %?
1 161,6 rpm, 58,08 Hz.
960 rpm, 48 Hz.
1200 rpm, 60 Hz.
What could be the probable cause if the reactive load sharing is balanced at low loads (up to 50 %), but imbalanced at higher loads?
The thyristor for one of the generators is broken.
Someone has adjusted the potmeter in the main switchboard. The result of this is that the imbalance will increase proportionally to the total load increase.
Loose connection or broken diode in one of the diode bridges. This will cause the regulator to increase the output to achieve UN = UG. The regulator can manage this at low loads, but a higher loads the capacity is not sufficient to compensate for the loss of one diode.
What does it mean if the synchronizing lamp rotation is counter-clockwise?
Generator frequency is to slow relative to main bus.
Generator frequency is to fast relative to main bus.
The voltage is wrong, but the frequency is correct.
What is the minimum requirement of isolation resistance for a 440 V system?
440 kilo Ohm.
220 kilo Ohm.
600 kilo Ohm.
No requirement at all.
What is the probable cause if the generator loads are balanced at low loads, but imbalanced at higher loads?
Dirty fuel oil filter on the diesel generator taking the smallest load.
Speed drop settings on the governors are not equalized.
The speed set points for the diesel generators are not equalized.
What will happen if load dependent start/stop of generator sets is in auto mode?
It will start/stop the generator sets in response to varying load.
It will start/stop the generator sets in response to fuel consumption.
It will start but never stop the generator sets in response to varying load.
It will stop but never start the generator sets in response to varying load.
Where will you find the instruments for synchronizing the generator?
On the main switchboard.
On the generator.
On the diesel engine.
On the circuit breaker.
Which control mode is recommended during manoeuvring?
Optimal, because this mode allows an increased load of the generators during manoeuvring.
Equal, because of the wider control range, which allows the low priority generator(s) to be connected at low loads.
Cyclic, because the risk of fouling of intake channels are eliminated, and because of this, the risks of reduced capacity of the generators are minimized.
Which of the following loads has the most negative effect (weaken) on the main field, and in doing so lowers the induced voltage in the generator?
Ohmic load.
Inductive load.
Capacitive load.
Which statement is true?
The Priority 1 generator will be first IN/first OUT.
The Priority 1 generator will be first IN/last OUT.
At Cyclic control mode the generators change Priority order.
Which statement is true?
When automatic frequency control is selected, the “follow-up” will parallel shift the speed drop until the generator frequency = nominal frequency.
The Power Management System can be considered as a back-up system for the main switchboard.
The Start/Stop request alarm activates and stops the diesel at low LO pressure.
Which statement is true?
Because it has fewer components, a brush/slip ring generator is preferred, because it minimizes the need for maintenance.
The electronic voltage regulator is installed as a back-up in case of breakdown of the primary current transformer.
For quick regulation at connection of large consumers, the load dependant primary winding produces an output corresponding to 120 % of nominal voltage.
The electronic voltage regulator will open the thyristor when more excitation current is necessary.
Which statement is true?
An engine room fan is considered an inductive load.
An electric heater is primarily a capacitive load.
When the load consists of ohmic, inductive and capacitive loads, there is no weakening of the main field since the loads will neutralize each other.
Why do we press the connect button when the synchroscope shows “5 to 12”?
The bus frequency will then “pull” the incoming generator into synchronism.
Connection at 12 may result in a reverse power trip on the incoming generator.
Because of the time delay (the time from pressing the button until the breaker is connected).



Test about Diesel Generator

Try online

Did you find mistake? Highlight and press CTRL+Enter

Март, 31, 2022 2751 0
SOC.MEDIA Telegram Vkontakte Facebook Odnoklassniki Instagram
Добавить комментарий